Schneider Electric Easy UPS 3L 400kVA 400V 3:3 UPS | 5×8 Start-Up | 1-Year Warranty | E3LUPS400KHS
The Easy UPS 3L 400kVA 400V 3:3 UPS (E3LUPS400KHS) is a high-capacity three-phase online uninterruptible power supply designed to provide reliable power protection for data centers, industrial facilities, electrical rooms, commercial buildings, and other mission-critical applications. It delivers 400kVA / 400kW of rated power with 400V three-phase input and output in a 3:3 configuration.
Featuring double-conversion online technology, the Easy UPS 3L continuously conditions incoming power to provide stable, high-quality power to connected equipment. The system uses an external battery configuration, allowing battery capacity and runtime to be selected according to the requirements of the installation.
The E3LUPS400KHS includes 5×8 startup service and Smart Test mode to help simplify commissioning and reduce startup time and costs. The Easy UPS 3L also supports parallel and redundant configurations and is designed for integration with Schneider Electric’s EcoStruxure power-management ecosystem.
- 400kVA / 400kW rated power
- 400V three-phase input and output
- 3:3 three-phase configuration
- Double-conversion online UPS topology
- External battery system
- 5×8 startup service included
- Smart Test mode
- Parallel and redundant configuration capability
- EcoStruxure-connected architecture
- Touchscreen LCD user interface
- IP20 protection rating
- Designed for critical power applications
160,472.00 AED
- 2 to 3 days-delivery
Speedy and reliable parcel delivery!
For Immediate delivery
For urgent delivery requirements, please contact our sales team. Standard shipping is typically within 2–3 days, with back-to-back orders taking 4–5 weeks. Product images are for illustrative purposes only.
Request a Quote
Documents
Click Here For Product Data Sheet
Easy UPS 3L 400kVA 400V 3:3 UPS (E3LUPS400KHS)
The Easy UPS 3L 400kVA 400V 3:3 UPS (E3LUPS400KHS) is a high-capacity three-phase online UPS designed to provide dependable power protection and business continuity for data centers, industrial facilities, commercial buildings, electrical rooms, telecommunications infrastructure, and other critical-power applications. With a rated capacity of 400kVA / 400kW, it is designed for demanding installations requiring high-capacity three-phase power protection.
The E3LUPS400KHS operates in a 3:3 three-phase configuration with a nominal 400V input and output. It also supports 380V and 415V configurations, providing flexibility for different electrical infrastructure requirements. The UPS uses double-conversion online technology to continuously regulate and condition the incoming power.
For demanding electrical environments, the UPS supports an input voltage range of 323V to 477V at full load and an input frequency range of 40–70Hz. The maximum input current for the 400V configuration is 719A, while the input power factor is greater than 0.99. Input harmonic distortion is specified at less than 3% for linear loads and less than 5% for non-linear loads.
The UPS uses an external battery system. The Easy UPS 3L platform supports 36–50 battery blocks, with a nominal battery voltage range of ±216V to ±300V. This external-battery architecture allows the battery configuration and required runtime to be selected according to the application’s requirements.
The E3LUPS400KHS includes 5×8 startup service, providing factory-authorized startup support. Schneider Electric also incorporates Smart Test mode, which is designed to simplify commissioning and help reduce startup time and deployment costs.
The Easy UPS 3L supports parallel and redundant configurations, providing flexibility for installations requiring additional capacity or increased availability. This makes the 400kVA model suitable for critical infrastructure where scalable and resilient power protection is required.
The UPS features a touchscreen LCD user interface for local monitoring and control. The EcoStruxure-connected architecture also enables integration with Schneider Electric’s power-management and monitoring solutions.
Output performance includes ±1% output voltage regulation, less than 2% output harmonic distortion with 100% linear loads, and less than 4% with 100% non-linear loads. The UPS supports 125% overload for 10 minutes and 150% for 1 minute.
The Easy UPS 3L 400kVA provides a combination of high power capacity, online double-conversion protection, external battery flexibility, Smart Test commissioning, 5×8 startup service and scalable redundancy, making it suitable for large-scale data-center, industrial and commercial power-protection requirements.
Key Features
- 400kVA / 400kW rated power
- 400V three-phase input and output
- 380V / 415V voltage configurations supported
- 3:3 UPS configuration
- Double-conversion online topology
- External battery system
- 36–50 battery blocks supported
- 5×8 startup service
- Smart Test mode
- Parallel configuration capability
- Redundant configuration capability
- EcoStruxure-connected architecture
- Touchscreen LCD user interface
- Input power factor greater than 0.99
- <3% input THDI for linear loads
- <5% input THDI for non-linear loads
- <2% output THDU with 100% linear load
- <4% output THDU with 100% non-linear load
- 125% overload for 10 minutes
- 150% overload for 1 minute
- IP20 protection
TECHNICAL SPECIFICATIONS
Click Here For Product Data Sheet
| Overview | |
|---|---|
| Presentation | Easy-to-configure, easy-to-use and easy-to-service 400 kVA 3 phase UPS with an exceptional combination of competitive specifications, compact footprint, and highly available parallel and redundant designs. The EcoStruxure connected Schneider Electric Easy UPS 3L is the easy choice for business continuity on your shop floor or in your electrical room. Includes 5×8 start-up service. |
| Main | |
| Main input voltage | 400 V AC 3 phases |
| Other input voltage | 380 V 415 V |
| Maximum input current | 719 A |
| Max short time withstand current | 35 kA |
| Input harmonic distortion | Less than 3 % for full load |
| Load power factor | 0.5 leading to 0.5 lagging without derating |
| Efficiency at full load | 323…477 V |
| Input frequency | 40…70 Hz |
| Output voltage | 400 V AC 3 phases |
| Other output voltage | 380 V 415 V |
| Rated power in W | 400 kW |
| Rated power in VA | 400 kVA |
| Maximum configurable power in VA | 400 kVA |
| Maximum configurable power in W | 400 kW |
| Output harmonic distortion | < 2% linear load and < 4% non-linear load |
| Output overload operation | 10 minutes at 125% and 60 seconds at 150% |
| UPS topology | Double conversion online |
| Output frequency | 50 Hz sync to mains 60 Hz sync to mains |
| Complementary | |
| Maximum short-circuit current | 35 kA |
| Battery type | Lead-acid external |
| Control panel | Touch screen LCD user interface |
| Color | White (RAL 9003) |
| Height | 197 cm |
| Width | 60 cm |
| Depth | 85 cm |
| Product weight | 538 kg |
| USB compatible | Yes |
| Provided equipment | Dust filter Installation manual Start-up service |
| Range of product | Easy UPS 3L |
| Product or component type | Uninterruptible power supply (UPS) |
| Environment | |
| Product certification | CE EAC RCM |
| Ambient air temperature for operation | 0…30 °C |
| Ambient air temperature for storage | -25…55 °C |
| Storage altitude | 0…14999.8 m |
| IP protection | IP20 |
| Relative humidity | 0…95 % non-condensing |
| Storage relative humidity | 0…95 % non-condensing |
| Acoustic level | 70 dB |
| Heat dissipation | 79181 Btu/h |
| Operating altitude | 0…4921 ft |
| Batteries & Runtime | |
| Battery type | External battery system |
| Battery voltage | +/- 216…+/- 300 V |
| Discharge battery voltage | +/- 172.8…+/- 240 V |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2117 mm |
| Package 1 Width | 1000 mm |
| Package 1 Length | 800 mm |
| Package 1 Weight | 584 kg |
| Contractual warranty | |
| Warranty (in months) | 12 |
Related products
APC Easy UPS On-Line 2000VA/1600W UPS | 2U Rackmount | 230V | LCD Display | Rail Kit Included | SRV2KRIRK
In stock
APC Smart-UPS SRT 10kVA Online Double Conversion UPS | Rackmount | 230V | Enterprise Power Protection | SRT10KRMXLI
In stock
APC Smart-UPS SRT 1500VA Online Double Conversion UPS | 2U Rackmount | 230V | SRT1500RMXLI
In stock
NVIDIA RTX 2000 Ada 16GB Graphics Card (4X61P69962) | 4×mini DisplayPort 1.4a | Ada Lovelace Architecture | 7680×4320@120Hz | 70W | 3-Year Warranty
Available on backorder
Schneider Electric Easy UPS 3L 300kVA 400V 3:3 UPS | 5×8 Start-Up | 1-Year Warranty | E3LUPS300KHS
In stock