Schneider Electric Easy UPS 3L 600kVA 400V | E3LUPS600KHSEasy UPS 3L 600kVA 400V 3:3 UPS | 600kVA | 400V | Startup 5×8 | E3LUPS600KHS

Easy UPS 3L 600kVA 400V 3:3 UPS (E3LUPS600KHS) is a high-capacity three-phase uninterruptible power supply designed for commercial and industrial applications requiring reliable power protection and business continuity. It provides a 600kVA capacity with a 400V three-phase input and output configuration and includes Startup 5×8 service. The Easy UPS 3L platform is designed for simplified selection, configuration, startup, operation and servicing.

  • 600kVA UPS capacity
  • 400V three-phase system
  • 3:3 three-phase input/output configuration
  • Easy UPS 3L platform
  • Startup 5×8 service
  • Designed for commercial and industrial applications
  • Robust electrical specifications
  • Ruggedized design features
  • Fault-tolerant design
  • Flexible redundancy schemes
  • Smart Test mode for faster deployment
  • Designed for simplified installation, operation and servicing

222,720.00 AED

Speedy and reliable parcel delivery!

For Immediate delivery

For urgent delivery requirements, please contact our sales team. Standard shipping is typically within 2–3 days, with back-to-back orders taking 4–5 weeks. Product images are for illustrative purposes only.

Documents

Click Here For Product Data Sheet


Easy UPS 3L 600kVA 400V 3:3 UPS (E3LUPS600KHS)

The Easy UPS 3L 600kVA 400V 3:3 UPS (E3LUPS600KHS) is a high-capacity three-phase online UPS designed to deliver dependable power protection and business continuity for large-scale data centers, industrial facilities, commercial buildings, telecommunications infrastructure, healthcare environments, transportation facilities, and other critical-power applications. With a rated capacity of 600kVA / 600kW, it is the highest-capacity model in the Easy UPS 3L 400V range.

The E3LUPS600KHS operates in a 3:3 three-phase configuration with a nominal 400V input and output. It also supports 380V and 415V configurations, allowing the UPS to be deployed across different electrical infrastructures. The system uses double-conversion online technology to continuously condition incoming power and provide a stable output to connected loads.

For demanding electrical environments, the Easy UPS 3L 600kVA provides a wide input voltage window of 323V to 477V at full load and supports an input frequency range of 40–70Hz. At 400V, the unit has a nominal input current of 921A and a maximum input current of 1079A. Input power factor is greater than 0.99, while input harmonic distortion is specified at less than 3% for linear loads and less than 5% for non-linear loads.

The UPS is designed for an external battery system. Schneider Electric specifies support for 36–50 battery blocks, with a nominal battery voltage range of ±216V to ±300V DC. The external-battery design allows the battery configuration and desired backup runtime to be selected according to the installation requirements.

The E3LUPS600KHS includes 5×8 startup service, providing professional startup support as part of the product configuration. Schneider Electric’s Smart Test mode helps simplify commissioning and can reduce deployment time and startup costs.

The Easy UPS 3L platform supports parallel operation up to 6+0 UPS units, allowing multiple systems to be configured to meet increased capacity or redundancy requirements. This provides flexibility for large critical-power installations where availability and scalability are important.

The system also supports ECO mode, which bypasses unused electrical components when power conditions are suitable to improve operating efficiency while maintaining protection. Schneider Electric specifies up to 96% efficiency for the Easy UPS 3L range.

For monitoring and management, the Easy UPS 3L includes a Network Management Card and supports EcoStruxure connectivity. The system also features an LCD graphics touchscreen display for displaying operating modes, system parameters and alarms.

The UPS has a standard IP20 protection rating with a dust filter. Schneider Electric offers an optional IP31 kit specifically for the 500kVA and 600kVA Easy UPS 3L models, providing additional protection for installations requiring it.

Output performance includes ±1% output voltage regulation, an output power factor of 1, and output harmonic distortion below 2% for 100% linear loads and below 4% for 100% non-linear loads. The UPS supports 105% continuous overload, 125% for 10 minutes and 150% for 1 minute at the specified operating conditions.

The APC Easy UPS 3L 600kVA 400V 3:3 UPS (E3LUPS600KHS) is therefore suited to large-scale power-protection installations requiring high capacity, external battery flexibility, scalable parallel operation, online double-conversion protection, professional startup support and centralized network monitoring.

Key Features

  • 600kVA / 600kW rated power
  • 400V three-phase input and output
  • 380V / 415V configurations supported
  • 3:3 UPS configuration
  • Double-conversion online topology
  • External battery system
  • 36–50 battery blocks supported
  • 5×8 startup service
  • Smart Test mode
  • Parallel operation up to 6+0 UPS units
  • Redundant configuration capability
  • ECO mode
  • EcoStruxure connectivity
  • Included Network Management Card
  • LCD graphics touchscreen display
  • Input power factor >0.99
  • <3% input THDI for linear loads
  • <5% input THDI for non-linear loads
  • <2% output THDU at 100% linear load
  • <4% output THDU at 100% non-linear load
  • 105% continuous overload
  • 125% overload for 10 minutes
  • 150% overload for 1 minute
  • IP20 protection with dust filter
  • Optional IP31 protection kit

TECHNICAL SPECIFICATIONS

Click Here For Product Data Sheet

Overview
Presentation Easy-to-configure, easy-to-use and easy-to-service 600 kVA 3 phase UPS with an exceptional combination of competitive specifications, compact footprint, and highly available parallel and redundant designs. The EcoStruxure Ready Schneider Electric Easy UPS 3L is the easy choice for business continuity on your shop floor, in your electrical room, or in your data center. Includes 5×8 start-up service.
Main
Main input voltage 400 V AC 3 phases
Other input voltage 380 V
415 V
Maximum input current 1079 A
Max short time withstand current 35 kA
Input harmonic distortion Less than 3 % for full load
Load power factor 0.5 leading to 0.5 lagging without derating
Cos phi 0.99
Efficiency at full load 323…477 V
Input frequency 40…70 Hz
Output voltage 400 V AC 3 phases
Other output voltage 380 V
415 V
Rated power in W 600 kW
Rated power in VA 600 kVA
Maximum configurable power in VA 600 kVA
Maximum configurable power in W 600 kW
Output harmonic distortion < 2% linear load and < 4% non-linear load
Output overload operation 10 minutes at 125% and 60 seconds at 150%
UPS topology Double conversion online
Output frequency 50 Hz sync to mains
60 Hz sync to mains
Complementary
Maximum short-circuit current 35 kA
Battery type Lead-acid external
Control panel Touch screen LCD user interface
Color White (RAL 9003)
Height 197 cm
Width 100 cm
Depth 85 cm
Product weight 720 kg
USB compatible Yes
Provided equipment Dust filter
Installation manual
Start-up service
Range of product Easy UPS 3L
Product or component type Uninterruptible power supply (UPS)
Environment
Product certification CE
EAC
RCM
Ambient air temperature for operation 0…30 °C
Ambient air temperature for storage -25…55 °C
Storage altitude 0…14999.8 m
IP protection IP20
Relative humidity 0…95 % non-condensing
Storage relative humidity 0…95 % non-condensing
Acoustic level 72 dB
Heat dissipation 126932 Btu/h
Operating altitude 0…4921 ft
Batteries & Runtime
Battery type External battery system
Battery voltage +/- 216…+/- 300 V
Discharge battery voltage +/- 172.8…+/- 240 V
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 211.5 cm
Package 1 Width 120 cm
Package 1 Length 101.5 cm
Package 1 Weight 768 kg
Contractual warranty
Warranty (in months) 12