APC GUTOR PXC IEC 80kVA, 3:3 400/400V, IP42, No Transformer, unitary or parallel redundant on option – GUPXC80H2
- Main Input/Output Voltage : 400 V 3 phases
- Wave type : Sine wave
- Bypass type : Built-in bypass
- Battery type : External battery system
- Warranty : 1-Year
PN : GUPXC80H2

Overview
High performance, compact 3 phase UPS power protection fully standardized for heavy industrial applications and harsh environments. Available in 3:3 and 3:1 configurations.


Detailed Tech Specification
Main
|
Main Input Voltage |
400 V 3 phases |
Other Input Voltage |
400 V |
Main Output Voltage |
400 V 3 phases |
Other Output Voltage |
400 V |
Rated power in W |
64000 W |
Rated power in VA |
80000 VA |
output connector type |
Hard wire 5-wire (3P + N + E) 1 |
Battery type |
External battery system |
provided equipment |
Dust filter
Installation guide
Network management card
User manual |
General
|
Bypass wiring configuration |
5 wire (3P + N + E) |
Bypass voltage tolerance |
+/- 10 % |
Max bypass input current |
128 A |
Bypass current protection |
160 A |
Number of power module free slots |
0 |
Number of power module filled slots |
0 |
Redundant |
No |
Physical
|
Height |
210 cm |
Width |
60 cm |
Depth |
80 cm |
Net weight |
460 kg |
Mounting preference |
No preference |
Mounting mode |
Not rack-mountable |
Two post mountable |
0 |
USB compatible |
No |
Input
|
network frequency |
45…65 Hz |
number of input connectors |
1 hard wire 5-wire (3P + N + E) |
input voltage limits |
360…440 V 400 V |
Maximum input current |
164 A |
Switching current capacity |
200 A |
Max short time withstand current |
65 kA |
Input harmonic distortion |
Less than 5 % for full load |
Input protection type |
Upstream protection according to source |
input current |
164 A per phase (3 phases) |
Load power factor |
0.5 leading to 0.5 lagging without derating |
Input Power Factor at Full Load |
0.98 |
Output
|
Maximum configurable power in W |
64000 W |
Harmonic distortion |
Less than 5 % |
output frequency |
50/60 Hz +/- 1 Hz sync to mains
60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised |
Crest factor |
Unlimited |
UPS type |
Double conversion online |
Wave type |
Sine wave |
Output voltage tolerance |
+/- 1 % |
Output harmonic distortion |
< 2% at 100% linear load and < 5% at 100% non-linear load |
Output overload operation |
10 minutes at 125% and 60 seconds at 150% |
Required output current protection |
160 A |
Neutral output current |
115 A |
Bypass type |
Built-in bypass |
efficiency |
94.6 % (full load)
94.9 % (half load)
93.9 % (in battery operation) |
Maximum configurable power in VA |
80000 VA |
Conformance
|
Product certifications |
CE |
Marking |
CE Mark |
standards |
IBC 2012
IEC 62040-1-1
IEC 62040-2
IEC 62040-3
ISTA 2B
VFI-SS-111 |
Environmental
|
Ambient air temperature for operation |
-10…40 °C |
relative humidity |
0…95 % non-condensing |
Operating altitude |
0…10000 ft |
Ambient air temperature for storage |
-30…70 °C |
storage Relative Humidity |
0…95 % Non-condensing |
Storage altitude |
0.00…4572.00 m |
Acoustic level |
65 dBA |
Heat dissipation |
12539 Btu/h |
IP degree of protection |
IP42 with air filter |
Batteries & Runtime
|
Number of battery filled slots |
0 |
Number of battery free slots |
0 |
Max current discharge |
208 A |
Battery power in VAH |
0 VAh runtime |
Extended runtime |
0 |
Communications & Management
|
Free slots |
1 |
Preinstalled device |
Network management card 2 with environmental monitoring, out of band access and Modbus |
control panel |
Multifunction LCD status and control console |
alarm |
Audible and visible alarms : prioritized by severity |
Emergency power off |
Yes |
Packing Units
|
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
230.0 cm |
Package 1 Width |
82.0 cm |
Package 1 Length |
108.2 cm |
Package 1 Weight |
536.61 kg |
Contractual warranty
|
Warranty |
1 year on-site repair or replace with factory authorized Start-Up |